description:
1.Standard
The products can be produced according to the standard GB9330-1988,and the factory can also manufacture the cable with other standards.
2.Scope of Application
The products are suitable for the connection of controlling electrical equipments and instrument meters,monitoring and controlling return circuit,protecting and measuring in power distribution unit under the circumstance that the rated voltage is up to 450/750V AC.
3.Type & Specification
Type Name Section Area(mm2) No.of core Application Site
KVV Copper Conductor,PVC Insulated and Sheathed Control Cable 0.75、1.0、1.5、2.5 2-16 Permanent installation indoors,incable ditches or plpes
4、6 2-14
10 2-10
KVVP Copper Conductor,PVC Insulated and Sheathed,Braiding Shielded Control Cable 0.75、1.0、1.5、2.5 2-61 Permanent installation indoors,incable ditches or plpes where shielding is required
4、6 2-14
10 2-10
KVVP Copper Conductor,PVC Insulated and Sheathed,Copper-tape Screened Control Cable 0.75、1.0、1.5、2.5 4-10 Permanent installation indoors,incable ditches or plpes where shielding is required
4、6 7-61
10 4-10
KVV Copper Conductor,PVC Insulated and Sheathed,Steel-tape Armoured Control Cable 0.75、1.0、1.5、2.5 7-61 Permanent installation indoors,incable ditches,pipes or under ground.Be able to bear stronger outer mechanical force
4、6 4-14
10 4-14
KVVR Copper Conductor,PVC Insulated and Sheathed Flexible Control Cable 0.5-2.5 4-61 Installation indoors where flexibility and movability are required
KVVRP Copper Conductor,PVC Insulated and Sheathed,Braiding Shielded Flexible Control Cable 0.5、0.75、1.0 4-61 Installation indoors where flexibility shielding and movability are required
1.5、2.5 4-48
KYJV Copper Conductor,XLPE insulated and PVC Sheathed Control Cable 0.75、1.0、1.5、2.5 2-16 Perm anent installation indoors,incable ditches or pipes
4、6 2-14
10 2-10
KYJVP Copper Conductor,XLPE Insulated,Braiding Shielded,PVC Sheathed Control Cable 0.75、1.0、1.5、2.5 2-61 Permanent installation Indoors,Incable ditches or pipes where shielding is required
4、6 2-14
10 2-10
KYJV22 Copper Conductor,XLPE Insulated,Steel-tape Armoured,PVC Sheathed Control Cable 0.75、1.0、1.5、2.5 7-61 Permanent installation indoors,incable ditches,pipes or underground,Be able to bear stronger outer mechanical force
4、6 4-14
10 4-10
KYJVP2 Copper Conductor,XLPE Insulated,Coppertape Screened,PVC Sheathed Control Cable 0.75、1.0、1.5、2.5 7-61 Permanent installation indoors,incable ditches or pipes where shielding is required.
4、6 4-14
10 4-10
KYJVR Copper Conductor,XLPE insulated,PVC Sheathed Flexible Control Cable 0.5-2.5 4-61 Installation indoors where flexibility and movability are required
KYJVRP Copper Conductor,XLPE insulated,Braiding Shielded,PVC Sheathed Flexible Control Cable 0.5、0.75、1.0 4-61 Installation indoors where flexibility shielding and movability are required
1.5、2.5 4-48


3.The Requirement for Using
(1).The long-time working temperature of conductor of PVC insulated cable is 70℃.
The long-time working temperature of conductor of XLPE insulated cable is 90℃.
(2).The temperature for laying the cables can not be lower than 0℃,Permissible curved radius(r)
Unarmoured cable:r≥6D;(D:outer diameter of the cable)
armoured or copper-tape screened cable;r≥12D;
shieldedflexible cable:r≥6D;

1.Brief introduction for PVC insulated & sheathed control cable
PVC insulated and sheathed control cable is suitable for connections of electric equipment in controlling,monitoring loop and circuit protecting at rated voltage up to and including 450/750V(A.C).The product has excellent characteristics not only in electric and mechanical purposes but in chemical corrosion resistance,heat-aging,environmental stress and flame-retardant.The product is simple in structure and convenient to use and could be laid with no restriction of different levels.
Our product of PVC insulated and sheathed control cable can be manufactured according to the Standard GB 9330-88 which is drawn up by reference to IEC 227 and 502 as well as the standards of west germany,America,Japan and U.S.S.R for control cable.We can also design and manufacture special control cable.We can also design and manufacture special control cable according to other standards or requirments of customers.
The properties of flame-retardant control cable are in accordance with the specifications in IEC 332-3. Type ZR-KVV of our control cable has been manufactured with various sizes.Welcome to choose our control cable.

2.Type and main applications of cable shown in Table 1.

Type Designation Main Applications
KVV Copper core PVC insulated and sheathed control cable For laying indoor,tunnels,ducts,conduit etc.permanent place
KVVP Copper core PVC insulated and sheathed copper wire shielded control cable For laying indoor,ducts,conducts etc,permanent place where shield is required.
KVVP2 Copper core PVC insulated and sheathed copper tape shielded control cable Ditto
KVV22 Copper core PVC insulated and sheathed steel tape armoured control cable. For laying indoor tunnels,ducts,conduit and direct burial etc.permanent place,able to bear great mechanical force
KVV32 Copper core PVC insulated and sheathed fine steel wire armoured control cable. For laying indoor,tunnels,ducts,conduct and shaft etc.permanent place,able to bear greater pulling force.
KVVR Copper core PVC insulated and sheathed flexible control cable. For laying indoor,and flexible required etc.place easy to move
KVVRP Copper core PVC insulated and sheathed copper wire braiding shielded flexible control cable For laying indoor and flexible and shield required etc.place.easy to move.
ZR-KVV Copper core PVC insulated and sheathed flame-redardant control cable For being applied on heat engine and heat controlling appliance.

3.Application
(1)Rated voltage Uo/U should be 450/750V
Uo-valid value of the voltage between main insulated conducotr and earthing(metal shield metal sheath or environment dielectric).
U-Valid value of voltage between any two phases conductor in multi core cable or single core calbe system.
When AC system is applied,the rated voltage of cable should be at least equal to the nominal voltage of the system when DC system is applied,the nominal voltage of this system should not be more than the rated voltage of the system by 1.5 times.
The operating voltage of system should not be more than the rated voltage of the system by 1.1 than the rated voltage of the system by 1.5 times.
(2)The permitted long-term operating temperature of cable conductor should be 70℃.
(3)The installing temperature of cable should not be less than 0℃,Recommending permitted bending radius:
Nonarmoured cable:not less than the overall diameter of cable by 6 times.
Armoured or copper tape shielded cable not less than the overall diameter of cable by 12 times.
Shielded flexible cable:not less than the overall diameter of cable by 6 times.
4.Delivery length
The ength of one coll should be 100M and not less tahn 100M on a drum allow to delivery length according to the agreement made by two sides.
The tolerance of delivery length should not more than ±5%.
5.Distinguish of insulated core and arrange drawing:
(1)Colour distinguish:
colours distinguish for the insulated core of 5 cores and below.
(2)Digits distinguish:
For the cable distinguished by digits,the colours of insulation and digits marks should be different distinctly so that it is easy to separate the cores in installing.The colour of insulation should be black,white,yellow,corresponding digits colour is white,black(blue),black(blue)etc.
7.Cable construction weight and main technical data shown in Table2-7
No of core
& nominal
cross Sec
mm2
Conductor
Construction
No./dia
mm
Nominal
insulation
thickness
mm
Nominal
sheath
thickness
mm
Overall
Dia
mm
weight
kg/km
Resistance
of conductor
at 20℃
Max.Ω/km
Insulation
resistance
at 70℃
Min.Ω/km
Test
voltage
V
3×0.75A
4×0.75A
5×0.75A
7×0.75A
8×0.75A
1/0.97
1/0.97
1/0.97
1/0.97
1/0.97
0.6
0.6
0.6
0.6
0.6
1.2
1.2
1.2
1.2
1.2
8.4
9.0
9.6
10.5
11.5
68
83
100
123
142
24.5
24.5
24.5
24.5
24.5
0.012
0.012
0.012
0.012
0.012
3000
3000
3000
3000
3000
10×0.75A
12×0.75A
14×0.75A
16×0.75A
19×0.75A
1/0.97
1/0.97
1/0.97
1/0.97
1/0.97
0.6
0.6
0.6
0.6
0.6
1.2
1.5
1.5
1.5
1.5
12.5
13.5
14.5
15.0
15.5
174
210
236
265
300
24.5
24.5
24.5
24.5
24.5
0.012
0.012
0.012
0.012
0.012
3000
3000
3000
3000
3000
24×0.75A
27×0.75A
30×0.75A
37×0.75A
44×0.75A
1/0.97
1/0.97
1/0.97
1/0.97
1/0.97
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.7
1.7
18.0
18.5
19.0
20.5
22.5
376
407
444
547
647
24.5
24.5
24.5
24.5
24.5
0.012
0.012
0.012
0.012
0.012
3000
3000
3000
3000
3000
48×0.75A
52×0.75A
61×0.75A
1/0.97
1/0.97
1/0.97
0.6
0.6
0.6
1.7
1.7
1.7
23.0
23.5
25.0
689
738
847
24.5
24.5
24.5
0.012
0.012
0.012
3000
3000
3000
3×0.75B
4×0.75B
5×0.75B
7×0.75B
8×0.75B
7/0.37
7/0.37
7/0.37
7/0.37
7/0.37
0.6
0.6
0.6
0.6
0.6
1.2
1.2
1.2
1.2
1.2
8.8
9.6
10.5
11.0
12.0
72
87
105
130
150
24.5
24.5
24.5
24.5
24.5
0.014
0.014
0.014
0.014
0.014
3000
3000
3000
3000
3000
10×0.75B
12×0.75B
14×0.75B
16×0.75B
19×0.75B
7/0.37
7/0.37
7/0.37
7/0.37
7/0.37
0.6
0.6
0.6
0.6
0.6
1.2
1.5
1.5
1.5
1.5
13.5
14.5
15.0
16.0
16.5
183
221
248
279
316
24.5
24.5
24.5
24.5
24.5
0.014
0.014
0.014
0.014
0.014
3000
3000
3000
3000
3000
24×0.75B
27×0.75B
30×0.75B
37×0.75B
44×0.75B
7/0.37
7/0.37
7/0.37
7/0.37
7/0.37
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.7
1.7
19.0
19.5
20.0
22.0
24.5
396
428
467
576
682
24.5
24.5
24.5
24.5
24.5
0.014
0.014
0.014
0.014
0.014
3000
3000
3000
3000
3000
48×0.75B
52×0.75B
61×0.75B
7/0.37
7/0.37
7/0.37
0.6
0.6
0.6
1.7
1.7
1.7
25.0
25.5
27.0
726
777
892
24.5
24.5
24.5
0.014
0.014
0.014
3000
3000
3000
3×1A
4×1A
5×1A
7×1A
8×1A
1/1.13
1/1.13
1/1.13
1/1.13
1/1.13
0.6
0.6
0.6
0.6
0.6
1.2
1.2
1.2
1.2
1.2
8.8
9.4
10.0
11.0
12.0
79
96
117
146
168
18.1
18.1
18.1
18.1
18.1
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
10×1A
12×1A
14×1A
16×1A
19×1A
1/1.13
1/1.13
1/1.13
1/1.13
1/1.13
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.5
1.5
14.0
14.5
15.0
15.5
16.5
223
248
280
316
360
18.1
18.1
18.1
18.1
18.1
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
24×1A
27×1A
30×1A
37×1A
44×1A
1/1.13
1/1.13
1/1.13
1/1.13
1/1.13
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.7
1.7
19.0
20.0
20.5
21.5
24.0
451
490
553
661
782
18.1
18.1
18.1
18.1
18.1
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
48×1A
52×1A
61×1A
1/1.13
1/1.13
1/1.13
0.6
0.6
0.6
1.7
1.7
1.7
24.5
25.0
26.5
835
896
1031
18.1
18.1
18.1
0.011
0.011
0.011
3000
3000
3000
3×1B
4×1B
5×1B
7×1B
8×1B
7/1.13
7/1.13
7/1.13
7/1.13
7/1.13
0.6
0.6
0.6
0.6
0.6
1.2
1.2
1.2
1.2
1.2
9.2
10.0
11.0
11.5
13.0
83
101
123
153
177
18.1
18.1
18.1
18.1
18.1
0.013
0.013
0.013
0.013
0.013
3000
3000
3000
3000
3000
10×1B
12×1B
14×1B
16×1B
19×1B
7/1.13
7/1.13
7/1.13
7/1.13
7/1.13
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.5
1.5
15.0
15.5
16.0
17.0
17.5
235
261
295
332
378
18.1
18.1
18.1
18.1
18.1
0.013
0.013
0.013
0.013
0.013
3000
3000
3000
3000
3000
24×1B
27×1B
30×1B
37×1B
44×1B
7/1.13
7/1.13
7/1.13
7/1.13
7/1.13
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.7
1.7
20.5
21.5
22.0
23.5
26.0
474
514
581
694
822
18.1
18.1
18.1
18.1
18.1
0.013
0.013
0.013
0.013
0.013
3000
3000
3000
3000
3000
48×1B
52×1B
61×1B
7/1.13
7/1.13
7/1.13
0.6
0.6
0.6
1.7
1.7
1.7
26.5
27.0
28.5
877
940
1082
18.1
18.1
18.1
0.013
0.013
0.013
3000
3000
3000

Table 2-2

No of core
& nominal
cross Sec
mm2
Conductor
Construction
No./dia
mm
Nominal
insulation
thickness
mm
Nominal
sheath
thickness
mm
Overall
Dia
mm
weight
kg/km
Resistance
of conductor
at 20℃
Max.Ω/km
Insulation
resistance
at 70℃
Min.Ω/km
Test
voltage
V
3×1.5A
4×1.5A
5×1.5A
7×1.5A
8×1.5A
1/1.38
1/1.38
1/1.38
1/1.38
1/1.38
0.7
0.7
0.7
0.7
0.7
1.2
1.2
1.2
1.2
1.5
9.8
10.5
11.5
12.5
14.5
104
128
157
198
247
12.1
12.1
12.1
12.1
12.1
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
10×1.5A
12×1.5A
14×1.5A
16×1.5A
19×1.5A
1/1.38
1/1.38
1/1.38
1/1.38
1/1.38
0.7
0.7
0.7
0.7
0.7
1.5
1.5
1.5
1.5
1.5
16.0
16.5
17.0
18.0
19.0
303
339
384
435
497
12.1
12.1
12.1
12.1
12.1
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
24×1.5A
27×1.5A
30×1.5A
37×1.5A
44×1.5A
1/1.38
1/1.38
1/1.38
1/1.38
1/1.38
0.7
0.7
0.7
0.7
0.7
1.7
1.7
1.7
1.7
1.7
22.0
22.5
23.0
25.0
28.0
645
701
768
923
1095
12.1
12.1
12.1
12.1
12.1
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
48×1.5A
52×1.5A
61×1.5A
1/1.38
1/1.38
1/1.38
0.7
0.7
0.7
1.7
1.7
2.0
28.5
29.0
31.5
1171
1258
1494
12.1
12.1
12.1
0.011
0.011
0.011
3000
3000
3000
3×1.5B
4×1.5B
5×1.5B
7×1.5B
8×1.5B
7/0.52
7/0.52
7/0.52
7/0.52
7/0.52
0.7
0.7
0.7
0.7
0.7
1.2
1.2
1.2
1.2
1.5
10.5
11.5
12.5
13.5
15.5
108
133
164
206
257
12.1
12.1
12.1
12.1
12.1
0.010
0.010
0.010
0.010
0.010
3000
3000
3000
3000
3000
10×1.5B
12×1.5B
14×1.5B
16×1.5B
19×1.5B
7/0.52
7/0.52
7/0.52
7/0.52
7/0.52
0.7
0.7
0.7
0.7
0.7
1.5
1.5
1.5
1.5
1.5
17.0
17.5
8.5
19.5
20.5
315
351
399
451
515
12.1
12.1
12.1
12.1
12.1
0.010
0.010
0.010
0.010
0.010
3000
3000
3000
3000
3000
24×1.5B
27×1.5B
30×1.5B
37×1.5B
44×1.5B
7/0.52
7/0.52
7/0.52
7/0.52
7/0.52
0.7
0.7
0.7
0.7
0.7
1.5
1.5
1.5
1.7
1.7
24.0
24.5
25.0
27.0
30.5
669
727
796
956
1134
12.1
12.1
12.1
12.1
12.1
0.010
0.010
0.010
0.010
0.010
3000
3000
3000
3000
3000
48×1.5B
52×1.5B
61×1.5B
7/0.52
7/0.52
7/0.52
0.7
0.7
0.7
1.7
1.7
2.0
31.0
31.5
34.0
1213
1302
1547
12.1
12.1
12.1
0.010
0.010
0.010
3000
3000
3000

Table 2-3

No of core
& nominal
cross Sec
mm2
Conductor
Construction
No./dia
mm
Nominal
insulation
thickness
mm
Nominal
sheath
thickness
mm
Overall
Dia
mm
weight
kg/km
Resistance
of conductor
at 20℃
Max.Ω/km
Insulation
resistance
at 70℃
Min.Ω/km
Test
voltage
V
3×2.5A
4×2.5A
5×2.5A
7×2.5A
8×2.5A
1/1.78
1/1.78
1/1.78
1/1.78
1/1.78
0.8
0.8
0.8
0.8
0.8
1.2
1.2
1.5
1.5
1.5
11.0
12.0
14.0
15.0
16.5
147
184
244
310
359
7.41
7.41
7.41
7.41
7.41
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
10×2.5A
12×2.5A
14×2.5A
16×2.5A
19×2.5A
1/1.78
1/1.78
1/1.78
1/1.78
1/1.78
0.8
0.8
0.8
0.8
0.8
1.5
1.5
1.5
1.7
1.7
18.5
19.0
19.5
21.0
22.0
441
498
568
663
761
7.41
7.41
7.41
7.41
7.41
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
24×2.5A
27×2.5A
30×2.5A
37×2.5A
44×2.5A
1/1.78
1/1.78
1/1.78
1/1.78
1/1.78
0.8
0.8
0.8
0.8
0.8
1.7
1.7
1.7
1.7
2.0
25.5
26.0
27.0
29.0
33.5
960
1049
1152
1383
1699
7.41
7.41
7.41
7.41
7.41
0.011
0.011
0.011
0.011
0.011
3000
3000
3000
3000
3000
48×2.5A
52×2.5A
61×2.5A
1/1.78
1/1.78
1/1.78
0.8
0.8
0.8
2.0
2.0
2.2
34.0
35.0
37.5
1820
1957
2296
7.41
7.41
7.41
0.011
0.011
0.011
3000
3000
3000
3×2.5B
4×2.5B
5×2.5B
7×2.5B
8×2.5B
7/0.68
7/0.68
7/0.68
7/0.68
7/0.68
0.8
0.8
0.8
0.8
0.8
1.2
1.2
1.5
1.5
1.5
9.4
13.0
14.5
16.0
17.5
155
194
259
327
379
7.41
7.41
7.41
7.41
7.41
0.009
0.009
0.009
0.009
0.009
3000
3000
3000
3000
3000
10×2.5B
12×2.5B
14×2.5B
16×2.5B
19×2.5B
7/0.68
7/0.68
7/0.68
7/0.68
7/0.68
0.8
0.8
0.8
0.8
0.8
1.5
1.5
1.5
1.7
1.7
19.5
20.5
21.5
23.0
24.0
467
525
599
701
803
7.41
7.41
7.41
7.41
7.41
0.009
0.009
0.009
0.009
0.009
3000
3000
3000
3000
3000
24×2.5B
27×2.5B
30×2.5B
37×2.5B
44×2.5B
7/0.68
7/0.68
7/0.68
7/0.68
7/0.68
0.8
0.8
0.8
0.8
0.8
1.7
1.7
1.7
1.7
2.0
28.0
28.5
29.5
31.5
36.0
1014
1107
1215
1468
1793
7.41
7.41
7.41
7.41
7.41
0.009
0.009
0.009
0.009
0.009
3000
3000
3000
3000
3000
48×2.5B
52×2.5B
61×2.5B
7/0.68
7/0.68
7/0.68
0.8
0.8
0.8
2.0
2.0
2.2
37.0
38.0
40.0
1919
2063
2421
7.41
7.41
7.41
0.009
0.009
0.009
3000
3000
3000

Table 2-4

No of core
& nominal
cross Sec
mm2
Conductor
Construction
No./dia
mm
Nominal
insulation
thickness
mm
Nominal
sheath
thickness
mm
Overall
Dia
mm
weight
kg/km
Resistance
of conductor
at 20℃
Max.Ω/km
Insulation
resistance
at 70℃
Min.Ω/km
Test
voltage
V
3×4A
4×4A
5×4A
7×4A
8×4A
1/2.25
1/2.25
1/2.25
1/2.25
1/2.25
0.8
0.8
0.8
0.8
0.8
1.2
1.5
1.5
1.5
1.5
12.5
14.0
15.0
16.5
18.0
198
268
331
426
494
4.61
4.61
4.61
4.61
4.61
0.0077
0.0077
0.0077
0.0077
0.0077
3000
3000
3000
3000
3000
10×4A
12×4A
14×4A
1/2.25
1/2.25
1/2.25
0.8
0.8
0.8
1.7
1.7
1.7
20.5
21.5
22.5
627
712
815
4.61
4.61
4.61
0.0077
0.0077
0.0077
3000
3000
3000
3×4B
4×4B
5×4B
7×4B
8×4B
7/0.85
7/0.85
7/0.85
7/0.85
7/0.85
0.8
0.8
0.8
0.8
0.8
1.2
1.5
1.5
1.5
1.5
13.5
15.0
16.5
17.5
19.5
206
279
345
442
514
4.61
4.61
4.61
4.61
4.61
0.0077
0.0077
0.0077
0.0077
0.0077
3000
3000
3000
3000
3000
10×4B
12×4B
14×4B
7/0.85
7/0.85
7/0.85
0.8
0.8
0.8
1.7
1.7
1.7
22.5
23.0
24.5
653
739
845
4.61
4.61
4.61
0.0077
0.0077
0.0077
3000
3000
3000